Lightning striking distance of complex structures
M. Becerra, V. Cooray and F. Roman
Abstract: Traditionally, the location of lightning strike points has been determined by using the
rolling sphere method, but recently the collection volume method (CVM) has also been proposed
for the placement of air terminals on complex structures. Both these methods are empirical in
nature and a more advanced model based on physics of discharges is needed to improve the
state of affairs. This model is used to evaluate the striking distance from corners and air terminals
on actual buildings and the results are qualitatively compared with the predictions of the rolling
sphere method and the CVM. The results show that the striking distance not only depends upon
the prospective return stroke current and the geometry of the building, but also on the lateral position of the downward leader with respect to the strike point. A further analysis is performed to
qualitatively compare the lightning attraction zones obtained with the CVM and the leader inception zones obtained for a building with and without air terminals. The obtained results suggest that
the collection volume concept overestimates the protection areas of air terminals placed on
complex structures, bringing serious doubts on the validity of this method.
1
Introduction
To determine the locations on a grounded structure that are
most vulnerable to be struck by lightning is the first step in
the design of an external lightning protection system.
Traditionally, the rolling sphere method [1], which is a
derivative of the electrogeometric method used in the lightning protection of power lines [2, 3], has been used to locate
the probable lightning strike points on buildings. The radius
of the fictitious rolling sphere is obtained as a function of
prospective return stroke peak current from an empirical
relationship that connects these two parameters.
Unfortunately, neither the concept of rolling sphere itself
nor the radius of the sphere adopted in the lightning protection of structures take into account any of the physical processes related to lightning strike. Indeed, the rolling sphere
method is nothing but a convenient compromise made in the
standardisation of committees [4].
The analysis of the lightning attractiveness of complex
structures used the physics of electrical discharges has not
yet been undertaken by the lightning researchers. This is
mainly due to the fact that the existing physics-based
upward leader inception models have not yet been properly
adapted to handle the problems when they are utilised
together with complex structures [5]. However, several
scientists have utilised semi-empirical models to study the
problem of lightning interception in complex structures.
Recently, D’Alessandro and Gumley [6] applied the collection volume concept proposed for free-standing rods and
transmission lines by Eriksson [7] to the analysis of lightning strikes to buildings. They combined this concept
# The Institution of Engineering and Technology 2008
doi:10.1049/iet-gtd:20070099
Paper first received 1st March and in revised form 12th May 2007
M. Becerra and V. Cooray are with the Division for Electricity and Lightning
Research, The Ångstrom Laboratory, Box 534, Uppsala University, Uppsala
SE 751 21, Sweden
F. Roman is with the Departamento de Ingenierı́a Eléctrica, Facultad de
Ingenierı́a, National University of Colombia, Ciudad Universitaria, Tv 38
No. 40-01 Edificio ‘Uriel Gutiérrez’, Bogota, Colombia
E-mail: marley.becerra@angstrom.uu.se
IET Gener. Transm. Distrib., 2008, 2, (1), pp. 131 – 138
with the field intensification method [8] to compute the
striking distance of lightning flashes in connection with
complex buildings. Even though the method is claimed to
be valid with field observations [9], there are doubts in
the lightning community on the validity of the collection
volume/field intensification method [10, 11]. Later, AitAmar and Berger [12] used a leader progression model
similar to the one proposed by Dellera and Garbagnati
[13] to study the lightning incidence to buildings. In their
analysis, the critical radius concept [14] was used as a condition for the initiation of upward connecting leaders from
buildings. However, this concept has been shown to be
inappropriate to evaluate the initiation of upward leaders
from structures without symmetry, as in the case of
buildings [15].
In order to more accurately evaluate the conditions
required for the inception of upward leaders from grounded
structures, a leader initiation model based on physics was
recently proposed by Becerra and Cooray [15]. This
model was successfully implemented to compute the background electric fields required to initiate upward leaders
from the corners of some complex buildings in Kuala
Lumpur [16]. A good correlation between the probable
points of leader inception and the observed lightning
strike points on the buildings was found. The study also
showed that the lightning strike points on a structure are
influenced not only by the prospective return stroke
current, as the rolling sphere method predicts, but also by
the geometry of the structure and its surroundings.
However, a comparative analysis of the results obtained
with the physical leader inception model and the rolling
sphere method was not performed in [16]. This is because
the downward stepped leader was not considered in that
analysis, therefore the striking distances from the studied
points could not be computed.
In order to improve the analysis presented in [16], the
downward moving stepped leader channel is considered in
this paper. The height of the leader tip at which a stable
upward leader is initiated from the analysed structure is
evaluated with the leader inception model presented in
[15]. Calculations are also made by varying the lateral
131
distance of the leader channel with respect to the building so
that the effect of corners of the buildings on the inception of
upward leaders can be elucidated. Particularly, the main
features of the leader inception zones as predicted by the
model and the predictions of the collection volume
method (CVM) [6] are also presented and discussed.
2
Evaluation of the leader inception condition
for complex grounded structures
2.1
Leader inception model
The evaluation of the initiation of upward stable leaders is
the first step in the analysis of lightning strike to grounded
structures. In order to identify the most likely lightning
strike points, it is necessary to evaluate the leader inception
condition on all the corners, edges and flat surfaces. To
overcome the restrictions of most of the existing leader
inception criteria when applied to complex structures, the
model introduced recently in [15] is used. This leader inception model simulates the first few metres of propagation of
an upward leader initiated from any structure with and
without axial symmetry. This model assumes that a stable
self-propagating upward leader is initiated at the moment,
when the background electric field is high enough to guarantee the leader advancement at least during the first few
metres. It is also assumed that the electric field produced
by the downward leader does not change considerably
during the time required for the initiation of the upward
leader. Therefore the complexity of a full dynamic leader
inception model [17] is avoided by considering this static
condition. This ‘static’ assumption leads to the underestimation of the striking distances compared with the dynamic
leader inception evaluation [17], where the time variation
of the background electric field produced by the descending
downward leader and the aborted streamer and leaders are
taken into account. In addition, it is assumed that the
initiation of streamers occurs before the leader inception
takes place (condition satisfied for corners with tip radius
smaller than some tens of centimetres). Thus, the following
simplified procedure is performed in order to evaluate
whether a stable leader is incepted or not under the influence
of a downward leader whose tip is at a given height:
1. The background potential distribution U1(0) produced by
the downward leader in front of the analysed point is
obtained by the methodology presented in Section 2.1.
This potential distribution U1(0) is calculated along the line
that connects the analysed point and the downward leader
tip. Then, the obtained potential U1(0) (z0 ) close to the analysed point (defined by z 0 ¼ 0) is approximated to a straight
line (Fig. 1) with slope E1 and intercept U 00 such that
U1(0) (z0 ) ’ E1 z0 þ U00
(1)
2. The charge DQ (0) and position ls(0) of the streamer corona
are computed as
DQ(0) ’ KQ
ls(0) ¼
U002
2 (Estr E1 )
U00
Estr E1
(2a)
(2b)
where KQ is a geometrical factor and Estr is the positive
streamer potential gradient. If the charge of the corona
burst DQ (0) is lower than 1 mC, it is not possible to create
the first leader segment. Therefore the leader inception
132
Fig. 1 Example of the linear approximation of a background
potential distribution from the corner of a building
condition will not be performed and the analysis stops in
this case. Otherwise, the simulation of the leader propagation starts at i ¼ 1 with an initial length lL(1) by the following steps:
(i)
3. The potential of the leader’s tip Utip
at the current simulation step i is computed as
(i)
¼ lL(i) E1 þ x0 E1
Utip
E
E E1 lL(i) =x0
e
ln str str
E1
E1
(3)
4. The position and charge of the corona zone in front of the
leader tip are calculated as
ls(i) ¼ ls(0) þ
(i)
Estr lL(i) Utip
Estr E1
(4a)
(i1)
(i)
DQ(i) ’ KQ {(Estr (lL(i) lL(i1) ) þ Utip
Utip
)
(ls(i1) lL(i) )}
(4b)
5. The leader advancement distance DlL(i) and the new
leader length lL(iþ1) are evaluated by using
DlL(i) ¼
DQ(i)
qL
lL(iþ1) ¼ lL(i) þ DlL(i) )
(5a)
(5b)
The values of the parameters used in (3) – (5) are shown in
Table 1.
6. If the leader length lL(iþ1) reaches a maximum value lmax ,
then the leader inception condition is fulfilled. If the leader
advancement DlL(i) starts decreasing after some steps, then
the leader will stop and the leader inception is not
reached. Otherwise, the analysis is continued by going
back to (c). A typical value of lmax equals to 2 m was
observed to be long enough to define the stable propagation
of an upward leader, when space charge pockets are not
considered [15]. Larger values require more analysis steps
and were shown to produce the same result.
2.2
Electrostatic calculation
The electrostatic calculation is the more demanding step in
the analysis, as discussed in [16]. In spite of the powerful
desktop computers and software availablity, the solution
of the Poisson equation in three dimensions (3D) still
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
Table 1: Constant parameters used for the evaluation
of the leader inception condition
Sym
Description
Value
Units
l (1)
L
initial leader length
5 1022
m
Estr
positive streamer gradient
4.5 105
V/m
E1
final quasi-stationary leader
3 104
V/m
0.75
m
65 1026
C/m
4 10211
C/V m
gradient
x0
constant given by the ascending
positive leader speed and the
leader time constant
qL
charge per unit length necessary
KQ
geometrical constant that
to thermal transition
correlates the potential
distribution and the charge in
the corona zone
Details about the chosen values can be found in [15]
requires a large amount of computational time and memory.
In this paper, a commercial finite element method (FEM)
program [18] is used to compute the potential distribution
from each corner of the analysed structure. Similar to the
calculations performed in [16], the main features of the analysed structure are drawn and the obtained FEM model is
placed inside an analysis volume. However, the stepped
leader is modelled instead of replacing it by an equivalent
quasi-uniform background field over the grounded structure
as in [16]. The downward leader is assumed to be a straight
vertical channel (without branching) whose charge density
is computed according to Cooray et al. [19].
Due to the restrictions in the number of mesh points, only a
finite analysis zone is considered, omitting the upper part of
the stepped leader. In addition, the side faces of the analysis
volume are defined as open boundaries, such that the tangential electric field on them is close to zero. Fig. 2 shows the
comparison of the computed potential distribution calculated
for the corner of a 90 m tall rectangular building, for different
sizes of the analysis volume. Since the maximum dimension
of most of the analysed structures did not exceed 100 m, the
analysis volume height is set equal to 600 m. Note that no
significant error on the computed potential distribution is
introduced when the upper part of the downward leader is
neglected and the lateral faces are far away as to be considered opened boundaries (case 600 m 1200 m 1200 m).
This is because the largest charge density in the leader
channel appears at its tip [19], and consequently the electric
field close to ground is mostly influenced by the lower part
of the downward leader. Nevertheless, as the width and
depth of the analysis volume is reduced (lower than
600 m 1000 m 1000 m), the assumption of a tangential
electric field equals to zero on those boundaries becomes
less valid, introducing significant errors on the computed
electric fields and potentials.
In the simulations, the contribution of the thundercloud
electric field is computed in a separate analysis volume.
For the sake of simplicity, the space charge layer created
by corona at the ground level is not directly taken into
account. This layer significantly shields the background
thundercloud electric field and influences the conditions
for initiation of upward stable leaders [20]. Because of the
space charge layer created during thunderstorms, electric
fields measured at the surface level are typically lower
than 10 kV m21 but they can be several times larger
above the ground level [21]. However, to keep a conservative approach in the estimation of the striking distance, a
uniform background electric field of 10 kV m21 (typical
value at ground level) is assumed. Thus, the upper face of
the geometry is set as a potential boundary with a value
given by the product of the background electric field and
the height of the analysis volume.
In order to obtain the proper solution of the 3D geometry,
it is necessary to use an adequate mesh and a solver. In the
former case, it is necessary to choose the mesh by compromising the quality and the number of elements. However,
numerical experiments showed that there are not large
differences between the results obtained with coarse and
fine meshes. In this paper, a normal mesh with maximum
element size scaling factor, element growth rate, curvature
factor and mesh curvature cut off equal to 1, 1.4, 0.4 and
0.01, respectively, is used. In addition, a maximum
element size of 4 m is defined along the line that defines
the downward leader in order to properly evaluate the
downward leader charge. Furthermore, different solvers
and preconditioners were tested to select the optimum
solver, which depends upon the type of the problem and
the available computational resources. In our case, the
best performance is obtained by using the conjugate gradients iterative solver with algebraic multigrid preconditioner
[18]. For a simple FEM model of a rectangular building, the
solution (including meshing) takes between 26 and 48 s
CPU time in a PC Intel Pentium, 3.19 GHz, 1.5 GB RAM.
2.3
Fig. 2 Computed potential distributions in front of a corner of a
90 m tall rectangular building under the influence of a downward
leader with prospective return stroke current of 10 kA and tip
height of 200 m above ground
Different dimensions (height, width and depth) of the analysis volume
are considered. The result with the full electrostatic calculation considering the whole downward leader channel and an analysis volume with
dimensions 4000 m 8000 m 8000 m is also plotted
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
Striking distance evaluation
In this paper, the critical height of the downward leader tip
zupward(i)
at which a stable upward leader is initiated from
0
the analysed point (xi , yi , zi) on the structure is computed
for different horizontal positions of the downward leader
(x0 , y0). For each case, the bisection method [22] is used
to find zupward(i)
in the interval given by the endpoint
0
values of zi þ 10 and zi þ 100. The considered interval is
chosen based on numerical experiments, where typical
values of the height of the downward leader tip zupward(i)
0
were found to range between the limits for prospective
return stroke currents lower than 30 kA. During each iteration, the FEM model is rebuild, remeshed and solved for
the corresponding downward leader tip height z0 . Then,
133
the potential distribution along the line that connects the
analysed point position (xi , yi , zi) and the considered position of the leader tip (x0 , y0 , z0) is computed and the
upward leader inception analysis presented in Section 2.1
is applied. In our calculations, up to seven iterations are
usually required to find the critical position of the downward leader tip (x0 , y0 , zupward(i)
) that leads to the initiation
0
of a stable upward leader for each case. In this paper, the
distance from the downward leader tip (x0 , y0 , zupward(i)
)
0
and the analysed corner (xi , yi , zi) at the moment of
upward leader inception is defined as the striking distance.
The analysis is performed for the vertices of each building since more than 90% of the observed lightning strike
points to buildings correspond to sharp and protruding
corners [23, 24]. For each corner, the location of the downward leader in the horizontal plane (XY ) is changed in order
to evaluate the influence of the lateral distance on the striking distance. It is evaluated from the position of the analysed corner (xi , yi) outwards, that the forming radial lines
spaced 458 until inception of upward leaders is not
reached. In this way, the places where the downward
leader incepts an upward leader define an area from each
corner which we define as the ‘upward leader inception
zone’. Even though this region does not correspond to the
‘effective lightning attraction zone’ of the structure [7],
the leader inception zone defines the upper limits of it.
This is because downward leaders located outside the
leader inception zone cannot initiate upward leaders from
the structure; therefore the connection of the downward
leader by the upward leader does not occur.
3
Case studies
In order to evaluate the striking distance of complex buildings, two of the case studies reported in [16] are modelled.
The first case study corresponds to the Faber Tower
Building shown in Fig. 3. This structure is formed by two
towers (H ¼ 90 m, W ¼ 30 m, L ¼ 70 m) adjacent to each
other and surrounded by another structure of similar
height of 100 m away. In this case, the striking distances
are computed for the labelled corners shown in Fig. 3.
The obtained position (x0 , y0 , zupward(i)
) of the downward
0
leader tip required to initiate an upward leader from each
corner are shown as asterisks. In the analysis, a downward
leader, which would result in a prospective return stroke
peak current of 15 kA is considered.
Interestingly, the model (Fig. 3b) predicts that the leader
inception zone of the corners does not define a symmetrical
and circular region in the horizontal plane as it is assumed
in the CVM [6]. Moreover, the major part of the leader inception zone of any given corner is located outside the building.
This suggests that most of the upward leaders incepted from
the corners are produced by the downward leaders located
outside the periphery of the structure. Whereas the stepped
leaders located above the building do not connect leaders
from the corners and consequently they strike the roof.
This result indicates that the corners of buildings do not effectively protect the building as proposed in [25], even if air
terminals or grounded metal caps are placed at the corners.
Nevertheless, the model shows that corners attract lightning
flashes towards the structure and this result is in agreement
with the observed fact that corners of buildings in Kuala
Lumpur and Singapure are struck by lightning flashes even
when air terminals are placed at the centre of the roof [23].
Another remarkable feature is that the longer striking distance of each corner does not correspond to the case where
the downward leader is located directly over the corner
(Fig. 3c) but to the cases where the position of the
134
Fig. 3 Diagram of the FEM model, the observed lightning
damaged points (dots) and the points of the downward leader tip
where leader inception takes place (asterisks) from the corners
of the Faber Tower Building
a 3D plot
b Top view
c Side view
The dotted lines define the upward leader inception zone whereas the
dashed lines define the hemispherical surface drawn with a radius
equal to the striking distance obtained for a downward leader
located directly over the corner, as assumed by the CVM [6]
downward leader tip is laterally displaced. Thus, the computed leader inception points (x0 , y0 , zupward(i)
) do not lie
0
on the hemispherical surface centred at the corners predicted by the CVM [6]. This result can be explained in
terms of the electric field produced by the downward
leader when it is placed at different positions with respect
to the corner of a grounded structure, as can be seen in
Fig. 4. Note, in this example that for three positions of the
downward leader tip (x0 , y0 , z0) equidistant to the corner P,
the obtained potential distributions are different. Moreover,
the potentials produced by a downward leader placed
outside the perimeter of the structure (case 3) are larger
than the ones produced by a downward leader located
above the corner (case 2). Since the potential distribution
is used to evaluate the leader inception and its propagation
during the first few metres, these differences manifest in the
computed striking distances presented in this paper.
A similar analysis is applied to the corners of two buildings in Kuala Lumpur (Bank Industry and Pembangunan)
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
Fig. 4 Example of a slice plot of the electric field logarithm
(upper plot) on the plane Y ¼ 0 produced by a downward leader
with a prospective return stroke current of 15 kA at three different
locations from the corner of a grounded structure.
The potential distribution along the line that connects the corner P and
each position of the downward leader tip (1, 2, 3) are also shown in the
lower plot
which have been observed to be struck by lightning for two to
five times during a period of 5 years. The buildings have
different heights (70 and 110 m) and are separated by
about 30 m. First of all, note that the computed leader inception zones are not symmetrical regions as in the previous
case. This is also the case for the air terminal T on the building roof (Fig. 5b) whose leader inception zone defines an
oval area different from the symmetric and circular attraction
zones of free-standing air terminals. This result shows that
the efficiency of air terminals on complex structures cannot
be evaluated based on studies performed for free-standing
rods [6, 7]. In addition, the length of the striking distance
changes from one corner to another depending upon the geometry of the building and the surroundings. This result
clearly suggests that the evaluation of the lightning incidence
of complex structures cannot be based on the prospective
return stroke current, as done in the case of the rolling
sphere method and its derivates. On the other hand,
the leader inception zone of the corners S and P of the
Pembangunam bank covers the corners C and B of the
Industry bank. This is in agreement with the fact that there
has not been observed any strike points in the corners C
and B during the period of observation [23]. This indicates
that the corners in tall structures could protect shorter adjacent structures and avoid lateral strikes. This result is in
agreement with field observations [23, 24].
4
Qualitative comparison with the collection
volume method
In 2001, D’Alessandro and Gumley [6] proposed the use
of the CVM for the optimum placement of air terminals
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
Fig. 5 Diagram of the FEM model, the observed lightning
damaged points (dots) and the points of the downward leader tip
where leader inception takes place (asterisks) from the corners
of two bank buildings: Industry and Pembangunan
a 3D plot
b Top view
c Side view
The dotted lines define the upward leader inception zone whereas the
dashed lines define the hemispherical surface drawn with a radius
equal to the striking distance obtained for a downward leader located
directly over the corner, as assumed by the CVM [6]
for the protection of grounded structures. The predictions
of this method are claimed to be in close agreement with
the actual strikes captured by designed lightning protection systems in Hong Kong [9] and Malaysia [26].
Based on the results presented in the previous section, it
is of interest to compare the predictions of the present
approach and the CVM for the same structure [6]. Even
though the leader inception zones computed in the
present work can only be qualitatively compared with
the lightning attraction zones defined by the CVM [6],
some conclusions can be drawn concerning the validity
of the CVM. It is important to stress that only a qualitative comparison can be done here due to the fact that the
physical approach presented in this paper involves the
upward leader inception only and does not consider
(yet) the propagation and successful connection of
upward and the stepped leaders.
135
Let us consider the CVM design example given in [6] as a
case study. It is a composite building formed by three rectangular volumes of dimensions 30 m 30 m 50 m,
15 m 20 m 20 m and 5 m 5 m 5 m as shown in
Fig. 6a. The analysis is performed for a prospective return
stroke current of 10 kA. Note that the leader inception
zones (Fig. 6b), with similar features as in the previous
section, are obtained in this case. These zones are not symmetrical areas centred at each corner as the attraction zones
predicted by the CVM (Fig. 6c). Instead, these zones mostly
cover the outer area on the periphery of the building, indicating that the corners of a building are more efficient to
protect adjacent structures than to protect the building
itself. In this way, the use of concentric attraction zones
for the corners of buildings, as it is suggested in [6], leads
to an overestimation of the lightning protection offered by
them. This result shows that the geometry of the collection
volume proposed by Eriksson [7] for rods and slender structures cannot be directly applied to define the attraction
zones of air terminals on complex structures, contrary to
what is assumed in [6].
Fig. 7 shows the lightning protection design given in [6]
for the same building, based on the CVM. Air terminals of
1 m tall were placed at ‘strategic locations’ (Fig. 7a) and the
striking distances of the corners (points A 0 , B 0 , C 0 and D 0 )
are slightly increased by placing 1 m tall air terminals on
them according to the calculations performed in [6]. The
striking distance corresponding to a stepped leader located
directly above the corner increases only about 8% by the
placement of such air terminal. The maximum striking distance (i.e., the largest striking distance observed when the
location of the stepped leader is moved laterally) increases
about 17% in comparison with the conditions pertaining to
the original building. However, the area of the leader inception zone of these points increases, as seen in Figs 6b and
7b. Even though the maximum striking distance does not
significantly change when the 1 m tall rods are placed at
the corners, the maximum lateral distance of the downward
leader tip that leads to the initiation of a stable upward
leader from them increases considerably, producing a larg
leader inception zone.
A similar result can be found for the air terminal on the
top of the building (point T 0 in Fig. 7b) in comparison
with the adjacent corner (point J in Fig. 6b). In this case,
the striking distances do not increase more than 9%. On
the other hand, the leader inception zone of the air terminal
T 0 is considerably smaller than the inception zones of the
outer corners (points A 0 , B 0 , C 0 and D 0 ), even though the
terminal is placed 5 m above these corners. This result
clearly shows that the larger leader inception zones are
not always associated with the highest points on a structure,
as one might expect intuitively.
It can be seen in Figs 6c and 7c that the CVM predicts an
increase in the maximum lateral attraction distance of more
than 100% where the air terminals are installed. Note that in
comparison with the leader inception zones shown in
Fig. 7b, the attractive zones predicted by the CVM are disproportionately larger in Fig. 7c, overestimating the lightning protection offered by the air terminals. Even though
the leader inception zones predicted in this paper do not
directly correspond to lightning attraction areas, similar features and proportions should apply for both cases. This is
also the case of the attraction area of the terminal T 0
which is comparable with the attraction zones of the outer
corners (points A 0 , B 0 , C 0 and D 0 ), contrary to the proportions between the leader inception zones shown in
Fig. 7b. Essentially, the excessive increase of the attractive
zones predicted by the CVM when air terminals are placed
136
Fig. 6 Comparison of the predictions obtained with the present
approach and the CVM for a composite building
a 3D plot of the analysed structure
b Leader inception zones obtained in this work
c Lightning attraction zones reported in [6]
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
on buildings is produced by the overestimation of the striking distances that are computed using the critical radius
concept and field intensification factors [6].
The presented results clearly show the large overestimations of the lightning attraction zones of air terminals predicted by the CVM when applied to complex grounded
structures [6] and cast serious doubts about the methodology of the analyses performed to validate that method
[9, 26]. In these publications, the statistics of actual
strikes captured by lightning protection systems in buildings
in Hong Kong [9] and Malaysia [26] are claimed to be in
good agreement with the number of strikes predicted by
the CVM. These analyses are mainly based on the assumption that the ground flash density of the site is known and
that the lightning attraction zone of the air terminals on
the complex structures considered is the same as that of
free-standing rods with the same height. Thus, the ground
flash density is computed from three different empirical
relationships, which are a function of the number of thunderstorm days per year of the site. The attraction zones
are defined by circular areas with a radius equal to the
attractive radius [7], which is a function of the prospective
return stroke peak current and the height of the structure.
Based on the attraction zones, the equivalent average lightning exposure area of the air terminals is computed by
taking into account the probability distribution of the prospective return stroke peak current. This exposure area
and the ground flash density are then used to obtain the
expected number of strikes per year. As the ground flash
density computed with the empirical relationships differed,
the value that produced a better agreement between the
computed expected number of strikes per year and the
actual number of strikes captured by the lightning protection system was used.
However, as it has been discussed in this section, the
attraction zones predicted by the CVM are excessively
large circular areas which do not agree with the present
results obtained with a more physically based approach.
Furthermore, the CVM neglects the fact that some parts
of a building are not fully protected by an air terminal on
a corner because of the asymmetry of the attraction zones.
For these reasons, it is expected that the lightning exposure
areas predicted by the CVM are larger than in reality and
that the good agreement between the number of strikes
per year estimated by the CVM and the observed number
of strikes [9, 26] is the result of a conveniently chosen
ground flash density.
5
Fig. 7 Comparison of the predictions obtained with the present
approach and the CVM for the same building analysed in Fig. 6
but ‘protected’ with 1 m tall air terminals placed according to
the CVM [6]
a 3D plot of the structure
b Leader inception zones obtained in this work
c Lightning attraction zones reported in [6]
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008
Conclusions
The striking distance of the corners of two actual complex
structures are computed by using a physical leader inception
model. The obtained results show that the striking distance
of complex structures not only depend upon the prospective
return stroke current, as it is assumed by the rolling sphere
method, but also depend upon the geometry of the building
and the lateral position of the downward leader with respect
to the strike point. Thus, it is found that the corners of
grounded complex buildings attract lightning flashes
towards the structure but do not initiate upward leaders to
intercept downward leaders located above the roof on
which they are located. This result agrees well with the
field observations in Kuala Lumpur and Singapore where
the corners of some buildings are struck by lightning [21].
In addition, it is found that the computed leader inception
zones and the lightning attraction zones of corners on buildings define asymmetric regions, contrary to the predictions
of the collection volume concept [6]. On the other hand, the
137
attraction zones defined by the CVM, as used in [6], and the
leader inception zones obtained in this paper are qualitatively compared and discussed for the case of a composite
building with and without air terminals. It is shown that
the collection volume concept [6] overestimates the lightning protection areas of air terminals placed on complex
structures. This result cast serious doubts about the validity
of the CVM for the placement of air terminals in buildings
[6] and on the analyses reported to validate that method
[9, 26].
6
Acknowledgment
This work is partly funded by the Swedish Research Council
(Grant no G-EG/GU 1448-306), the Swedish Rescue
Services Agency (Grant no. 012-7039-2003) and a donation
to Uppsala University by John and Svea Andersson.
7
References
1 Szedenik, N.: ‘Rolling sphere: method or theory?’, J. Electrost., 2001,
51– 52, pp. 345–350
2 Armstrong, H.R., and Whitehead, E.R.: ‘Field and analytical studies
of transmission line shielding’, IEEE Trans., 2001, PAS-87,
pp. 270–279
3 Brown, G.W., and Whitehead, E.R.: ‘Field and analytical studies of
transmission line shielding: part II’, IEEE Trans., 1969, PAS-88,
pp. 617–625
4 Horvath, T.: ‘Standarization of lightning protection based on the
physics or on the tradition’, J. Electrost., 2004, 60, pp. 265– 275
5 Darveniza, M.: ‘A modification to the rolling sphere method for
positioning air terminals for lightning protection of buildings’. Proc.
25th Int. Conf. Lightning Protection, 2000, (ICLP Rhodes Greece),
pp. 904–908
6 D’Alessandro, F., and Gumley, J.R.: ‘A collection volume method for
the placement of air terminals for the protection of structures against
lightning’, J. Electrost., 2001, 50, pp. 279– 302
7 Eriksson, A.J.: ‘An improved electrogeometric model for transmission
line shielding analysis’, IEEE Trans., 1987, PWDR-2, pp. 871–886
8 Petrov, N.I., and Waters, R.T.: ‘Determination of the striking distance
of lightning to earthed structures’, Proc., R. Soc. A, 1995, 450,
pp. 589–601
9 Petrov, N.I., and D’Alessandro, F.: ‘Assessment of protection system
positioning and models using observations of lightning strikes to
structures’, Proc., R. Soc. A, Math. Phys. Eng. Sci., 2002, 458,
pp. 723–742
10 Mousa, A.M.: ‘Proposed research on the collection volume method/
field intensification method for the placement of air terminals on
138
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
structures’. Power Engineering Society General Meeting, 2003,
vol. 1, pp. 301– 305
Hartono, Z.A., and Robiah, I.: ‘The field intensification method: an
assessment based on observed bypass data on real buildings in
Malaysia’. Report Submitted to Standards Australia Committee
EL-024, September 2002
Ait-Amar, S., and Berger, G.: ‘A 3D numerical model of negative
lightning leader inception: application to the collection volume
construction’. Proc. 25th Int. Conf. Lightning Protection, France,
2004, (ICLP Avignon), pp. 357– 362
Dellera, L., and Garbagnati, E.: ‘Lightning strike simulation by means
of the leader progression model, part I: description of the model and
evaluation of free-standing structures’, IEEE Trans., 1990,
PWRD-5, pp. 2009– 2023
Carrara, G., and Thione, L.: ‘Switching surge strength of large air
gaps: a physical approach’, IEEE Trans., 1979, PAS-95, pp. 512 –524
Becerra, M., and Cooray, V.: ‘A simplified physical model to
determine the lightning upward connecting leader inception’, Trans.
IEEE Power Deliv., 2006, 21, pp. 897– 908
Becerra, M., Cooray, V., and Zainal, H.: ‘Identification of the
lightning vulnerable points on complex grounded structures’,
J. Electrost., 2006, 65, pp. 562– 570
Becerra, M., and Cooray, V.: ‘Time dependent evaluation of the
lightning upward connecting leader inception’, J. Phys. D: Appl.
Phys., 2006, 39, pp. 4695–4702
Comsol Group, FEMLAB User Guide, 2005
Cooray, V., Rakov, V., and Theethayi, N.: ‘The lightning striking
distance – revisited’, J. Electrost., 2007, 65, pp. 296–306
Becerra, M., Cooray, V., Soula, S., and Chauzy, S.: ‘Effect of the
space charge layer created by corona at ground level on the
inception of upward lightning leaders from tall towers’, J. Geophys.
Res., 2007, 112, D12, D12304
Standler, R.B., and Winn, W.P.: ‘Effects of coronae on electric fields
beneath thunderstorms’, Q. J. R. Meteorol. Soc., 1979, 105,
pp. 285–295
Press, W.H., Flannery, B.P., Teukolsky, S.A., and Vetterling, W.T.:
‘Numerical recipes: the art of scientific computing’ (Cambridge
University Press, Cambridge, UK, 1986)
Hartono, Z.A., and Robiah, I.: ‘A method of identifying the lightning
strike location on a structure’. Int. Conf. Electromagnetic
Compatibility, 1995, (ICEMC), pp. 112– 117
Hartono, Z.A., and Robiah, I.: ‘The collection surface concept as a
reliable method for predicting the lightning strike location’. Proc.
25th Int. Conf. Lightning Protection, Greece, 2000, (ICLP Rhodes),
pp. 328–333
Hartono, Z.A., and Robiah, I.: ‘A study of non-conventional air
terminals and striken points in a high thunderstorm region’. Proc.
25th Int. Conf. Lightning Protection, Greece, 2000, (ICLP Rhodes),
pp. 357–361
D’Alessandro, F., and Petrov, N.I.: ‘Field study on the interception
efficiency of lightning protection systems and comparison with
models’, Proc., R. Soc. A, Math. Phys. Eng. Sci., 2006, 462,
pp. 1365–1386
IET Gener. Transm. Distrib., Vol. 2, No. 1, January 2008